YNS water cooling screw chiller
Category:
Features
Product Details
Product performance
The water-cooled chiller is small in size and large in cooling capacity. It adopts a world-famous imported compressor, with excellent low-temperature performance, reliability and durability. The product is designed according to the characteristics of industrial applications. It has a built-in low-temperature circulating water pump and a stainless steel refrigerated water tank, which is extremely convenient to use. All materials are made of anti-corrosion materials, which can effectively prevent rust and corrosion. Microcomputer LED quantity controller, with temperature display, set temperature, automatic adjustment of freezing water temperature and compressor delay protection function, select brand-name contactors, relays and other electrical components , Equipped with perfect indicator lights, switches, the operation is clear at a glance, built-in electronic water level indicator and alarm device, low water level automatic alarm, the operator can grasp the water level of the frozen water tank through the control panel, and replenish water in time, the unique modular design, each The system of each compressor is safe and independent. Even if one system fails, it will not affect the normal operation of other systems.
1. The compressor of the unit adopts the original imported brand of French Maneurop (Meiyoule), American Copeland (Copeland)/Carrier (Carrier), Germany BITZER (Bitzer) and other medium and low temperature compressors;
2. Use refrigerants such as R404A, R410a, R22/R407C, etc. to meet the cooling temperature and environmental protection requirements;
3. Temperature selection range: process chilled water between -5℃~-60℃ can be provided (users can choose unit specifications with different outlet water temperatures according to different production needs;
4. According to the needs of users, a variety of refrigerants (chilled water) can be selected: alcohol refrigerants such as ethylene glycol aqueous solution, alcohol, ternary mixed solution, etc., or the evaporator can be designed according to anti-corrosion requirements, using chlorinated water. Aqueous calcium solution.
Basic parameters of YNS water cooling screw chiller
Model |
YNS | |||||||||||
100.1 | 135.1 | 180.1 | 195.1 | 235.1 | 260.1 | 305.1 | 320.1 | 350.1 | 385.1 | |||
Nominal refrigeration capacity |
KW | 100 | 135 | 180 | 195 | 235 | 260 | 305 | 320 | 350 | 385 | |
104Kcal/h | 8.6 | 11.6 | 15.5 | 16.8 | 20.3 | 22.4 | 26.3 | 27.6 | 30.2 | 33.2 | ||
Run control |
PLC fully-automatic control |
|||||||||||
Power Supply | 380V/3N~/50Hz | |||||||||||
Compressor |
Model |
5-6 asymmetric semi-closed double-screw compressor |
||||||||||
Quantity |
1 set |
|||||||||||
Start type |
Y-Δ start |
|||||||||||
Energy regulation |
0-33-66-100% | 0-25%-50%-75%-100% | ||||||||||
Input power |
KW | 22.6 | 29.8 | 37.3 | 41 | 49.9 | 54.3 | 61.1 | 64.3 | 70.8 | 78 | |
Rated current |
A | 39.3 | 51.9 | 64.9 | 71.3 | 86.8 | 94.5 | 106.3 | 111.9 | 123.2 | 135.7 | |
Evaporator |
Model |
Efficient dry-type shell and tube heat exchanger |
||||||||||
Water flow rate |
m3/h | 17.2 | 23.2 | 31 | 33.6 | 40.6 | 44.8 | 52.6 | 55.2 | 60.4 | 66.4 | |
Piping diameter |
DN65 | DN80 | DN100 | DN125 | ||||||||
Water pressure drop |
Kpa | 48 | 48 | 50 | 50 | 50 | 52 | 54 | 55 | 55 | 58 | |
Condenser |
Model |
Efficient shell and tube heat exchanger |
||||||||||
Water flow rate |
m3/h | 21.5 | 29 | 38.7 | 41.9 | 50.5 | 55.9 | 65.6 | 68.8 | 75.3 | 82.8 | |
Piping diameter |
DN65 | DN80 | DN100 | DN125 | ||||||||
Water pressure drop |
Kpa | 46 | 46 | 47 | 47 | 48 | 49 | 51 | 53 | 53 | 56 | |
Refrigerant |
Type |
R22 | ||||||||||
Filling quantity |
kg | 20 | 25 | 30 | 40 | 45 | 49 | 52.2 | 60 | 65 | 75 | |
Overall dimension |
Length |
mm | 2283 | 2495 | 2517 | 2825 | 2822 | 2778 | 2767 | 2750 | 3147 | 3070 |
Width |
mm | 700 | 900 | 900 | 900 | 900 | 900 | 900 | 900 | 900 | 900 | |
Height |
mm | 1489 | 1450 | 1557 | 1570 | 1700 | 1700 | 1850 | 1852 | 1880 | 1890 | |
Unit weight |
kg | 850 | 1050 | 1270 | 1340 | 1640 | 1680 | 1720 | 1750 | 2080 | 2300 | |
Operating weight |
kg | 900 | 1150 | 1420 | 1540 | 1890 | 1940 | 1990 | 2050 | 2330 | 2550 |
- Parameters under nominal working conditions are as follows: temperature of incoming and outgoing chilled water 12℃/ 7℃; temperature of incoming and outgoing cooling water 30℃/ 35℃;
- Temperature condition: outgoing chilled water temperature scope 5℃~ 15℃, cooling water temperature scope 19℃~ 33℃;
- The designed pressure bearing capacity of the water side of the evaporator and condenser is 1.0MPa;
- The dirt coefficient on the water side of the evaporator under the nominal working condition is 0.018m2℃ /kW, and that on the water side of the condenser is 0.044m2℃ /kW;
- In addition to the aforesaid specifications and requirements, the Company can provide non-standard products as needed by customers.
ONLINE MESSAGE