YKN square countercurrent open cooling tower
Category:
Features
Product Details
Product performance
1. Standard design conditions: dry bulb temperature 31.5°C, wet bulb temperature 28°C, atmospheric pressure 99400Pa, inlet water temperature 37°C, outlet water temperature 32°C;
2. The special packing for inclined trapezoidal wave square tower is selected, which has excellent thermal performance and small ventilation resistance, so that this type of cooling tower can achieve the design purpose of compact structure and small footprint;
3. The counter-flow square cooling tower adopts the airfoil-shaped hollow structure with large diameter, large area, low speed and low dynamic pressure FRP fan blades. The use of this type of cooling tower has the remarkable characteristics of energy saving and low noise;
4. The ultra-low noise cooling tower is equipped with noise reduction devices at the air inlet and rain area, so that the cooling tower of the same level can effectively reduce the noise by 5dB (A);
5. It can be combined in parallel in various forms, which is more suitable for the use of circulating cooling water systems with large amounts of water;
6. The fixed water distribution system is adopted, and the ABS multi-layer flow low-pressure water sprinkler is selected, which has uniform water distribution, long service life, and low water distribution head, which is beneficial to save the water distribution power of the system;
7. Q-235 profiles and FRP profiles can be used for the frame of the counter-flow square cooling tower. Although the construction period is slightly longer and the one-time investment is higher, it has excellent properties such as long service life and low maintenance cost.
Users can choose according to the actual situation;
8. If the turbidity of circulating water is higher than 50ppm for a long time, or contains impurities such as oil pollution, PVC grid packing should be selected according to the water quality conditions. The turbidity of this packing can be extended to 450pm for circulating water.
YKN Square Countercurrent Open Cooling Tower Parameter Table
Model |
Overall dimension (mm) |
Cooling water flow rate m3/h |
Fan φmm |
Motor KW |
Weight KG |
Noise decibel |
|||||
Length (L) |
Width (W) |
Height (H) |
Tower body H1 |
Air drum H2 |
Dead weight Dry |
Operation Wet |
db | ||||
YKN-100 | 2460 | 2460 | 4280 | 3240 | 760 | 100 | 1800 | 4 | 1250 | 2320 | 61 |
YKN-125 | 2460 | 2460 | 4430 | 3390 | 760 | 125 | 1800 | 4 | 1350 | 2497 | 62 |
YKN-150 | 2760 | 2760 | 4720 | 3590 | 820 | 150 | 2100 | 5.5 | 1420 | 2627 | 63 |
YKN-175 | 2760 | 2760 | 4720 | 3590 | 820 | 175 | 2100 | 5.5 | 1520 | 2812 | 63.5 |
YKN-200 | 3370 | 3370 | 4930 | 3260 | 1000 | 200 | 2400 | 5.5 | 1770 | 3770 | 63.5 |
YKN-250 | 3370 | 3370 | 5270 | 3560 | 1000 | 250 | 2400 | 7.5 | 1830 | 2890 | 64 |
YKN-300 | 3980 | 3980 | 5160 | 3380 | 1000 | 300 | 3000 | 11 | 2960 | 6590 | 64 |
YKN-350 | 3980 | 3980 | 5680 | 3900 | 1000 | 350 | 3000 | 11 | 3150 | 6790 | 64 |
YKN-400 | 4895 | 4895 | 5330 | 3260 | 1200 | 400 | 3400 | 15 | 3450 | 7090 | 65 |
YKN-450 | 4895 | 4895 | 5480 | 3410 | 1200 | 450 | 3400 | 15 | 4680 | 9760 | 65 |
YKN-500 | 4895 | 4895 | 6070 | 3900 | 1200 | 500 | 3400 | 15 | 5420 | 12320 | 66 |
YKN-600 | 5810 | 5810 | 5850 | 3650 | 1200 | 600 | 3600 | 18 | 5730 | 12960 | 66 |
YKN-700 | 6725 | 6725 | 5650 | 3650 | 1000 | 700 | 42710 | 22 | 6890 | 16310 | 67 |
Steel open tower, parameters on request.
ONLINE MESSAGE